Product description: Technical Specifications: 3 Detection Circuits, each compatible with up to 25 CPD-705x, PSD-715x or THD-705x detectors
  Two independently programmable  Agent Releasing Circuits
  Three sophisticated programmable  Notification Appliance Circuits
  5.4 Amp Power Supply Unit
  Clean Agent, Sprinkler, Deluge/ Pre-Action, Foam and Foam/Water  systems compatible   Features: ? Built-in Class A supervision for all    circuits can be achieved without    additional hardware. ? Triple-R? redundancy safeguards     the system from inadvertent    suppression activation. ? Release Countdown Timer alerts     you to precisely when the system    will discharge. ? Password Protection ensures     system integrity by preventing     unauthorized access. Approvals: CFMus to NFPA 72, ANSI/UL864, 9th edition and ULC-S527-99 CSFM Approved  MEA Approved cULus to ANSI/UL864, 9th edition  and ULC-S527-99    |